A tree has raised and cracked a section of the
sidewalk, corrective action is necessary in order to avoid injury.
Improvements to surface water controls are necessary to avoid water
infiltration. Regrade the soil around the perimeter of the home to
encourage surface water to drain away from the foundation walls. Remove
debris from gutters and downspouts regularly and configure their
discharge so they effectively discharge water at least 10 feet from the
home.
EXTERIOR & ROOF
The roof covering is in very poor condition. I feel it is well
beyond the end of its useful life. It is unlikely the existing roof
covering is or will be water tight. Although some roofing materials in
this condition MAY function for a short time, near term replacement of
the roofing and flashing should be anticipated. Prior to expiration of
your inspection contingency further evaluation by a roofing contractor
is necessary to determine the scope and cost of replacement.
When roofing replacement is performed sound construction practice and
the local building department may require removal of all the existing
asphalt and cedar roof coverings (all garage and part of home). New
sheathing (additional expense) and roof covering will then be required
to be installed.
I showed you water stains on the underside of the roof sheathing and
roof rafters. Prior to expiration of your inspection contingency either
obtain a written guarantee from the owner stating all necessary
corrective action has already been performed OR obtain a written
guarantee from the owner stating all the necessary corrective action
will be performed, in order to avoid additional damages and surprises
after closing. Sometimes latent water, insect and other damages exist,
in addition to those I could see today. Read the LATENT DAMAGES MAY
EXIST and the INDOOR AIR QUALITY FUNGUS, MILDEW AND MOLD sections of
this report. If leaks are not cured promptly mold, mildew and fungus may
grow, wood destroying insects and rot damage should also be expected to
occur.
Insulation was installed against the under side of the roof
sheathing, although not recommended, it was done often. Sometimes
condensation forms on the roof sheathing and roof structure,
accelerating deterioration of the roof sheathing, roof structure and
reducing the life expectancy of the roof shingles. Sheathing and roof
framing hidden by insulation will not be found by today's visual
inspection. In order to determine if latent damages exist, destructive
or invasive testing must be performed.
No front stair handrail exists, one should be installed in order to
avoid injury.
No visible signs of water infiltration were observed to be occurring
today though the roofing, windows or siding (other than specified).
Water infiltration may occur during precipitation even though no visible
signs of water infiltration were observed today. You must either
contract for invasive and destructive testing (prior to expiration of
your inspection contingency) or accept the risk that latent water
infiltration may be occurring.
STRUCTURE
The garage was full of storage, if problems exist I was not able to
see them due to excessive storage. Wood earth contact exists around the
perimeter of the garage. It is necessary to regrade the exterior in
order to provide at least 8" of clearance between the siding and
the soil in order to help avoid further damages from rot, insects and
water. Latent damages may occurring that I was not able to see today due
to installed interior and exterior finishes. Invasive testing is
necessary to determine if damages or problems have already occurred.
Wood destroying insect activity was observed within the wood
structure of the home. MAY be necessary. Please be aware additional
latent damage to the structure of the home may exist that was not
discovered during today's visual inspection of the accessible
components. Sometimes repairs are expensive. I was not able to determine
if latent damages exist, because I was not contracted to perform
invasive or destructive testing (such as opening of walls or ceilings,
lifting of carpets or area rugs or ceiling tiles or insulation, moving
of furniture or appliances or stored items or debris), or excavation. In
order to determine if latent damages exist, it is necessary to have
invasive and destructive testing and further evaluation by experienced
contractors and specialists (prior to expiration of your inspection
contingency period) to define the scope & cost of any necessary
corrective action. Homeowner's loath the idea of invasive and
destructive testing because it is costly, messy and it can expose latent
damages that can be expensive to repair. Obtain written documentation
from an expert to determine the extent of wood destroying insect damage
that has occurred. Obtain a treatment and repair history from the owner.
Front and side porch framing is lighter than expected, installation
of additional supports is necessary to avoid injury.
The master bathroom shower has a cracked wall tile. There is a
separation between the master bathroom floor tile and base tile. The
master and main bathroom floors tilt as does the flooring at the top of
the stairs. Water stains exist on the kitchen ceiling below as does
evidence of several patches. I suspect problems exist behind finishes
that I was not able to see or report on today. Prior to expiration of
your inspection contingency, it is necessary for you to obtain further
examination and analysis by a qualified, insured and reputable
specialist, tradesman or service technician to define the scope &
cost of the necessary corrective action.
Closed walls, suspended and fixed ceilings in the lower level of this
structure, blocked access to 85% of the wood framing for inspection.
Latent wood destroying insect, water or other damage that could not be
seen during today's visual inspection may exist behind these finishes
that represent open ended risks to you.
Typical movement of the floors, walls and ceilings was observed for a
home of this age and construction style (other than specified). Problems
may still exist with the structure that were not detected by today's
visual inspection. You must either contract for invasive and destructive
testing (prior to expiration of your inspection contingency) or accept
the risk that latent defects exist that were not discovered during
today's visual inspection.
No active water infiltration was observed during today's inspection
(other than specified). Water infiltration may occur during
precipitation. Latent water infiltration may be occurring, you must
either contract for invasive and destructive testing (prior to
expiration of your inspection contingency) or accept the risk that
latent defects exist that were not discovered during today's visual
inspection.
Implement the changes recommended in the GROUNDS & EXTERIOR
sections of this report to help keep the basement drier.
You are reminded to obtain and maintain a wood destroying insect
treatment warranty and to obtain annual wood destroying insect
inspections. Wood destroying insects should be expected to infest or
reinfest any home without any warning. If you do not obtain and maintain
a treatment warranty with annual inspections you run a real risk of
paying for a treatment in the future and sustaining damage to the
structure. To help avoid wood destroying insect infestation keep wood
debris, mulch and firewood away from the home, slope soil away from the
home to provide drainage, remove any soil from contact with siding, keep
trees and shrubs trimmed well away from the home.
ELECTRIC
Wires were improperly installed that are not secured to the
structure, wires were improperly installed in contact with plumbing and
heating pipes, wires were improperly installed in contact with heating
equipment smoke pipes, open junction boxes exist, junction boxes with
too many wires exist and ground wires are improperly secured to the sub
panel enclosure without the required terminal strip. These conditions
are fire and shock hazards that require immediate corrective actions.
Improperly wired (reversed polarity, ungrounded three prong, etc.)
receptacles were found in the home. Corrective action by an electrical
contractor is necessary in order to cure the existing unsafe condition
and hazard.
As typical for a home of this age portions of an old type (knob and
tube) wiring system MAY exist. Knobs and tubes are visible in the
basement, ungrounded receptacles exist within the home. Check with your
insurance agent to determine if this type wire will be an issue with
your home owners insurance company, I have been told it is likely to be
an issue. Prior to expiration of your inspection contingency it is
necessary to have the condition of the wiring further evaluated by an
electrical contractor to determine if it is still safe for use or if it
should be replaced to lessen the risk of fire and shock. If any of the
wiring is covered by insulation it MUST be replaced due to the elevated
risk of fire.
There is no electric receptacle in the first floor powder room,
installation of a GFCI protected receptacle is recommended in order to
avoid electric shock. I could not locate or test the Jacuzzi to
determine if the required and necessary GFCI protection exists. The
GFCI's in the main and master bathroom did not trip when tested.
Corrective actions are necessary to avoid electric shock.
Visible electrical modifications and changes exist that were
improperly installed, additional latent defects are likely to exist.
Prior to expiration of your inspection contingency it is necessary for
you to contract for further evaluation by a state licensed electrical
contractor to further investigate the scope of work required to correct
all the above listed unsafe conditions and to determine if additional
corrective actions are necessary. Changes and upgrades are necessary to
make the home safe, as is replacement of all amateur electrical work.
Permits and inspections should be obtained from the municipality.
HEATING & AIR CONDITIONING
From the ground it appears the required spacing between the chimney
flue liners does not exist. It also appears the chimney bricks are
cracked through. Cracked and loose bricks also exist within the
fireplace fire box. There is a separation at the fireplace lintel. The
fireplace lacks a modern smoke chamber type configuration, it may be too
smoky to use. Prior to expiration of your inspection contingency, it is
necessary for you to obtain further examination and analysis by a
qualified, insured and reputable specialist, tradesman or service
technician to define the scope & cost of the necessary corrective
action because the above listed conditions may be hazardous and
dangerous.
Only part of the home is serviced by the air conditioning system, it
may not be very effective.
The home is heated by oil, an underground tank is on the property.
Prior to expiration of your contingency period, make sure you have the
tank tested and obtain insurance coverage to protect against tank
leakage.
The air conditioning condenser is not level, it should be leveled in
order to avoid premature failure. The air handler in the attic is
dripping into the overflow pan, the interior drain may be clogged or
damaged. The air conditioning system must be cleaned, adjusted, repaired
and tested by a qualified person. The service person must be asked to
provide certification it is operating effectively after the necessary
corrective action has been taken, or perform the necessary replacement(s),
prior to expiration of your inspection contingency.
The old steam boiler is beyond its statistical useful life. I can not
predict when failure will occur, budget for near term replacement.
Although excluded from our contract insulation on the boiler and/or
distribution piping is similar in appearance to materials known to
contain asbestos. Although there is a very high probability the material
is asbestos, it is simply not possible to visually determine if the
material is asbestos with absolute certainty, laboratory analysis is
necessary. If the insulation contains asbestos it was improperly removed
by amateurs. Consultation with a licensed asbestos contractor is
necessary prior to expiration of your inspection contingency to
determine the proper course of action and to obtain an opinion as the
necessity of air or bulk samples. Due to the age of construction, there
may be other materials within the home that contain asbestos but are not
identified by this inspection report. Asbestos fibers that get into the
air represent a health hazard.
During the inspection I turned up the thermostat for the steam
boiler. When the boiler turned on the smoke alarms went off due to a
smoke condition. In order to avoid damaging the home or boiler I
immediately shut the boiler off. I was not at all able to test the
boiler or steam heating system. The boiler and heating system must be
cleaned, adjusted, repaired and tested by a qualified person. The
service person must be asked to provide certification it is operating
effectively and safely after the necessary corrective action has been
taken, or perform the necessary replacement(s), prior to expiration of
your inspection contingency.
PLUMBING
The water heater is old, it is beyond its statistical useful life. I
can not predict when failure will occur, budget for near term
replacement.
I smelled gas in the area of the gas meter. I requested PSE&G be
contacted. PSE&G responded and the service person indicated no leak
exists. Because you also smelled gas it is necessary to have a PSE&G
supervisor or plumbing contractor determine if a hazardous gas leak
exists and to take the necessary corrective actions.
Access to the gas meter and entry piping has been improperly
obstructed by a cabinet, alterations to the cabinet are necessary.
BATHROOMS
Installed finishes blocked access to the Jacuzzi motor and
equipment, access must be provided for inspection, service and repair to
determine if problems or hazards exist. Because the drain control was
not operational I was not able to test the Jacuzzi to determine if it is
operational or water tight. Make sure it is repaired and that you test
it during your walk through.
The bathrooms have electric heaters, keep combustibles away from the
heaters and leave the doors open during cold weather to avoid frozen
pipes and damages.
The windows near the Jacuzzi is not tempered or safety glass, upgrade
the windows in order to avoid injury.
See additional bathroom comments under the STRUCTURE section of this
report
KITCHEN
No additional comments
INTERIOR
The existing smoke detectors are inadequate. At a minimum they must
be upgraded to the satisfaction of the municipality. Although not
required by law, I recommend the installation of at least one ceiling
mounted smoke detector on every floor of the home, in the halls within
ten feet of every bedroom and inside every bedroom. The additional smoke
detectors will increase your chances of surviving a fire for a minimal
cost.
Evidence of rodent activity was noted. Consult a pest control
specialist to determine the scope and cost of the necessary clean up and
corrective action.
The existing attic guardrails are inadequate or missing, cure these
conditions to avoid injury. To avoid injury guardrails must be secure,
at least 36" high and have vertical openings less than 4"
wide. Horizontal members that child could climb are unsafe.
The existing attic ventilation is inadequate, improving attic
ventilation may help avoid ice damming and increase the useful life of
the roof covering.